This time we introduce a company specializing in plastic injection located in Dali District, Taichung City.
The evaluation information is as follows:
Total: 20 traditional dual-tube T5 fluorescent lamps and 7 traditional 250W mercury lamps
According to the floor plan and photos provided by the customer, the simulation is reversed (Area AB)
Apply the simulation to evaluate the illuminance value of the AB area
Estimate the illuminance value of the working surface in the AB area
Simulated illuminance value of zone C
Illuminance value of working surface in zone C
The actual simulation uses 100 watts and 150 watts, and applies three angles to confirm that the two most suitable wattages and angles are available for customers to choose.
After the simulation and deduction of the actual application of the lamps, we suggest that the 150-watt UFO high patio lamp should be used as the basis.
The reasons for the establishment of the instrument are as follows:
The 150-watt high patio light can be used to individually control the lamps to increase the brightness, and the 150-watt patio light can improve the overall illuminance and the practicality of pre-lighting in the area.
On the contrary, if you choose a 100-watt high patio light, you need to turn it on all at once and turn it on separately. After the 100-watt high patio light is updated, the illumination can be increased to a minimum requirement of 300Lux.
When opened alone, the illumination will be as low as 175Lux. (This is suitable for storage, storage and logistics illumination)
It is more suitable for the abutment operator to replace the 100 watts and then the actual application needs to be fully opened.
After multiple selections and cross-assessment, the on-site survey will be confirmed!
----------------------------------------------------------------------------------------
The actual survey mainly confirms the simulation and installation contents:
Area A: Use traditional double-lamp traditional T5 fluorescent tubes, total: 4 traditional T5 fluorescent lamps
Area B: Use two-lamp traditional T5 fluorescent lamps and a group of 250W mercury lamps, total: 10 traditional T5 fluorescent lamps and 5 mercury lamps.
Zone C: Use traditional dual-lamp T5 lamps and 250W mercury lamps, a total of 6 traditional dual-lamp T5 fluorescent lamps and 2 250W mercury lamps
Lamp installation height is about 5.5 meters
In the AB area, the traditional T5 lamp is fully turned on, and the traditional mercury lamp is not turned on, the measured illuminance under the lamp is about 85Lux, (this illuminance is about the same as the basement parking lot illuminance)
Under the condition that the traditional T5 lamp is fully turned on in the AB area and the traditional mercury lamp is not turned on, the measured illuminance under the lamp is about 85Lux.
The lamps are not suitable for use, this time to replace the LED can improve the overall brightness and reduce electricity bills.
----------------------------------------------------------------------------------------
If you don't understand the meaning of illuminance, you can refer to the brightness of the office.
----------------------------------------------------------------------------------------
This LED replacement has a lot of content that needs to be confirmed. Our company provides confirmation of the construction plan.
----------------------------------------------------------------------------------------
Due to the inability to use aerial work vehicles throughout the site, the crane installation operation is relatively slow!
Working at heights requires a full-body double-hook seat belt!
Dismantled old lamps and transformers are concentrated.
The above LED high patio light installation case.